Features:
Lapp Kabel 16001313 H07RN-F Heavy-duty, rubber-sheathed cable, High stresses
Heavy-duty, rubber-sheathed cable; High stresses; Allowed up to 1000 V (0.6/1 kV) alternating voltage within protected and fixed installation; Arrangements from single core rubber-sheathed cables H07RN-F can be used for short-circuit and short-to-ground proof installation in accordance with VDE 0100 Part 520
Application range:
• Hand-held and power supply devices acc. HD 516/ VDE 0298-300
• Tools and agricultural machinery acc. HD 516/ VDE 0298-300
• Dry and damp interiors as well as outdoors acc. HD 516/ VDE 0298-300
• Light & Sound technology
FEATURES:
• Heavy-duty, rubber-sheathed cable
• High stresses
• Bare copper wire according to HAR
• Core insulation: Rubber Type EI 4
• Outer jacket of rubber Type EM2
• Flame retardant according to IEC 60332-1-2
• Oil resistant according to EN 60811-2-1
• Allowed up to 1000 V (0.6/1 kV) alternating voltage within protected and fixed installation
• Arrangements from single core rubber-sheathed cables H07RN-F can be used for short-circuit and short-to-ground proof installation in accordance with VDE 0100 Part 520
SPECIFICATION:
• Part number: 16001313
• Number of cores and mm2 per conductor: 5 x 6
• Outer diameter in mm max.: 17,5 - 22,2
• Copper index kg/m: 0,288
• Weight kg/m approx.: 0,760
• Minimum bending radius: 133,2 mm
• Core identification code: According to VDE 0293-308 (Appendix T9)
• Conductor stranding: Fine wire according to VDE 0295 Class 5/ IEC 60228 Class 5
• Rated voltage: U0/U: 450/750 V
• Test voltage: 2500 V
• Specific insulation resistance: 1 GOhm x cm
• Range of temperature: Occasional flexing: -25°C up to +60°C
• Current rating: According to VDE 0298 part 4 Tab. 11 and 13
• Approvals: VDE 0282 Part 4 / HD 22.4 S4