Features:
EN 54-16 Voice Alarm Extension Amplifier 240W / 100V
Specifications:
Power Source AC mains, 50/60 Hz DC: 24 V DC
Power Consumption 600W
Rated Output 240W
Frequency Response 50 – 20,000 Hz, ±3dB (at 1/3 rated output)
Distortion Under 0.8% (at rated output, 1kHz)
Signal-to-Noise Ratio Over 85dB
Input External Amp Input : 100V LINE Plug-in screw connector
Audio Input -50 dB (MIC)/-10 dB (LINE) (changeable) 600?, electronically balanced plug in screw connector
Output Speaker output 1 – 2 : max (360w) per output
Speaker output 3 - 6 : max (120w) per output
Total with in 240W
Direct output : Direct output from internal or external amplifier
VM Link RJ45 female connector
VM LINK IN : for connecting the VM-3240VA or VM-3360VA
VM LINK OUT : for connecting the VM-3240E or VM-3360E
Maximum distance : 800 m
Link cable: Cat. 5 Shielded Twisted-Pair straight cable (CAT5-STP)
EXT PA Link RJ45 female connector for connecting the VP-2241 or VP-2421
Maximum distance : 5 m
Link cable: Category 5 Shielded Twisted-Pair straight cable (CAT5-STP)
General Control In: 1 – 8/Out: 1 – 8
Input : No-Voltage make contact input, open voltage: 24V DC, short-circuit current: under 1 mA
Output : Isolated open collector output, withstand voltage: 30V DC, operating current: under 50 mA
Emergency Control In: 1 – 6/Status out
Input 1 – 5 : No-Voltage make contact input, open voltage : 24V DC, short-circuit current: under 2 mA
Connection resistance to make the function: Inactive; 9.4kOhm ±5%/Active; 4.7kOhm ±5%
Input 6: Isolated voltage input: Inactive; -24V ±20%/Active; +24V ±20%
Status out: Relay contact output, withstand voltage: 40V DC, operating current: 2 – 300mA
ATT Control Plug In connector, relay contact, 30V DC, 125V AC 5A (AC/DC)
Power In/Out
PS Out/DC Power In M4 Screw terminal
This connector for connecting the VX-2000DS only
DC 28V/20A (operating range: 20 - 40V DC)
DS Link RJ45 connector for connecting the VX-2000DS
Dimensions 482 (W) x 132.6 (H) x 460 (D)mm
Weight 16.5kg