Features:
EN 54-16 Voice Alarm System Amplifier
Specifications:
Power Source AC mains, 50/60 Hz DC: 24 V DC
Power Consumption 600W
Rated Output 240W
Frequency Response 50 – 20,000 Hz, ±3dB (at 1/3 rated output)
Distortion Under 0.8% (at rated output, 1kHz)
Signal-to-Noise Ratio Over 85dB
Audio Input/Output
Characteristic Sampling frequency: 48kHz
A/D D/A CONVERTER: 24bit
Input Input 1 – 3 : -50 dB (MIC)/-10dB (LINE) (changeable) 600Ohm, electronically balanced
Input 4: -50 dB (MIC)/-10 dB (LINE) (changeable) 600Ohm, electronically balanced
BGM 1–2: -10 dB, 10kOhm RCA pin jack
External AMP Input: 100V Line plug in screw connector
Output Speaker output 1–2: max (240W) per output
Speaker output 3 - 6 : max (120W) per output
Total with in 240W
Direct output: Direct output from internal or external amplifier
Recording output BGM/Paging: 0dB, 10k?,
RM Link 1.2 in 2 RJ45 for connecting the RM-300MF/RM-200M Remote Microphone.
Maximum distance: RM1.2 Total 800 m
Link cable: Cat. 5 Shielded Twisted-Pair straight cable
Network I/F RJ45 connector for switching hub or PC
10 BASE-T/100 BASE-TX Circuit
Maximum distance: 100m between this unit and a switching hub or PC
Link cable: Cat. 5 Shielded Twisted-Pair straight cable
VM Link RJ45 for connecting the VM-3240E or VM-3360E
Maximum distance: 800 m
Link cable: Cat. 5 Shielded Twisted-Pair straight cable
EXT PA Link RJ45 for connecting the VP-2241 or VP-2421
Maximum distance : 5 m
Link cable: Cat. 5 Shielded Twisted-Pair straight cable
General Control In: 1 – 8/Out: 1 – 8
Input : No-Voltage make contact input
Output : Isolated open collector output
Emergency Control In: 1 – 6/Status out
Input 1 – 5 : No-Voltage make contact input
Input 6: Isolated voltage input
Status out: Relay contact output
DC24V Output 24V DC ±10%, Max. 0.4A
DS Link RJ45 for connecting the VX-2000DS
Maximum distance: 5 m
Link cable: Cat. 5 Shielded Twisted-Pair straight cable
Dimensions 482 (W) x 132.6 (H) x 460 (D)mm
Weight 16.5kg